Winter operation of evaporative
condensers.
Many refrigeration plants operate in geographic regions
where ambient temperatures fall below freezing. There are two measures to
prevent the spray water from freezing in such instances:
1.
To locate the sump in a warm area.
2.
To drain the water from the condensers and operate the condensers
dry.
The
indoor sump must be able to accommodate all of the water normally in suspension
in the condenser during operation. The cost of pumping spray water will be
slightly higher than experienced when the sump is integrated to the condenser
because of the additional head attributable to the differences in elevation
between the condenser and the sump. However, water pump operation during the
cold weather will improve the efficiency of a refrigeration plant. Condenser
power (pumps, fans) of wet operation will be lower than the condenser power of
dry operation. This means that water pumps should be operated as long as
possible, though at subzero temperatures fan blades can freeze.
Centrifugal fans use more energy than axial fans, but
they are less sensitive to subzero temperatures. If your refrigeration plant has
condensers with centrifugal and axial fans, condenser sequence should be
different during summer and winter operation. During summer operation the
condensers with axial fans should run first in order to save energy. During
winter operation the condensers with centrifugal fans should run first to
prevent the fan from freezing and to maximize the efficiency of the
refrigeration plant.
During winter, some people may prefer the dry (water
pumps off) operation of evaporative condensers. One incentive for a plant to
shift to dry operation is that the costs of water treatment can be eliminated. I
have found that energy costs of dry operation are typically greater than those
of water treatment savings. A refrigeration plant should be switched to dry
operation when ambient temperature is 30 degC or lower.
Some plants can have low head pressure even when
condenser pumps and fans are off. The reason for this low head pressure is low
refrigeration load and cold strong wind. The valve off of the condensers can
help to increase the head pressure. Nonetheless, I wound not recommend this
action, as many evaporative condensers do not have the safety relief valves.
Cold valved off condenser can be filled up with liquid ammonia. During a sudden
weather warm up, a condenser can be damaged if the valves are not opened. I
recommend wind shields to prevent low head pressure during winter
operation.