Air in
ammonia system
Air
may enter a system through leaks in seals, gaskets, or uncapped valves when
suction pressure of refrigeration plant is negative (lower than atmospheric
pressure). Another way that air gains access to the system is when refrigeration
system was opened.
Usually, compressor manufacturers recommend using vacuum
pump to evacuate a compressor after opening. I would not suggest this step
because the mechanical seal of this compressor can start leaking after
evacuation. Air drawn into the system is eventually pumped to condenser where
the liquid seal prevents it from traveling further.
The
presence of air in condensers penalizes the system performance through the
artificial elevation of the condensing pressure. The air adds partial pressure
to that of the refrigerant pressure and thus increases the pressure against
which the compressor must work. Energy use of this compressor will increase. A
further penalty is the reduction in the heat-transfer coefficient by requiring
the refrigerant to diffuse through the air on its way to the tube surface where
it condenses.
A
test of the need for purging is to compare the actual head pressure and
saturation pressure at the temperature of ammonia condensate flowing from
condenser to high pressure receiver or to thermosyphon receiver. If the actual
pressure is significantly higher than the saturated pressure corresponding to
condensate temperature, purging should be done.
Usually, the refrigeration plants with positive suction
pressures do not have air purgers. Manual purging can be done from time to time
based on comparison of actual head pressure and saturated pressure at the
condensate temperature.
Example.
A refrigeration plant operates at
head pressure of 140 psig. Temperature of condensate flowing
from condenser is 75 °F. Corresponding pressure to that
temperature is 125 psig. 140 - 125 = 15
psig can
be purged from this refrigeration plant and new head pressure will be around
125
psig.
Automatic purgers are a necessity for refrigeration plants
with negative suction pressures. These purgers proceed from one purge point
to another to extract the air. Usually, the purge points are located above the
liquid ammonia surfaces (condensers, thermosyphone receivers, high pressure
receivers), where air concentration is maximal. To minimize air leaks into the
system, the suction side of these plants should be pressurized (pressure above
atmospheric) from time to time and tested for ammonia leaks.