Verification of energy
savings
In
industrial refrigeration, energy can be saved by improving efficiency of
refrigeration plants. The efficiency of refrigeration system is commonly
expressed as total horsepower (including the power input of compressors,
evaporator fans, condenser fans and condenser pumps) per ton of
refrigeration.
E = HP / R
Efficiency improvement should be verified by field
testing of refrigeration plant. Power consumption can be measured before and
after improvement. However, in real life it is difficult to measure
refrigeration capacity of a refrigeration plant. How can we verify the energy
efficiency improvement?
Majority, usually over 90
%, of energy savings are
instantaneous. As soon as energy saving measures is implemented, we can see the
result in a short period of time. Some measures (hot gas defrosting
optimization, load shifting) are not visible within a short period of time, but
their share in total energy savings are not significant.
To
verify energy efficiency improvement, we have to measure power consumption of
refrigeration plant during a short period of time.
The
following steps should be done:
1.
Measure power consumption of
original refrigeration plant. Time is 1 hour.
2.
Energy efficiency measures
are implemented. Transition period is 0.5 hour.
3.
Measure power consumption of
improved refrigeration plant. Time is 1 hour.
4.
Compare power consumption in
step 1 and step 3.
Major requirement for correct testing is constant
refrigeration load. This load should not change within 2.5 hours of
testing.
Cold storages usually have a steady refrigeration load.
It is not difficult to test this type of refrigeration plants. Production
facilities should run a steady production during 2.5 hours of testing. Try to
avoid defrosting in this period.
Example. In a previous newsletter I have mentioned about
refrigeration plant with 3 condensers. Condenser 1 has fan power 40
HP and it is equipped with fan VFD. Condensers 2, 3 have fan power
80 HP
each. Testing of this plant should be done
as following:
1.
Run
condenser 1 at 100 %
speed and cycle condenser fan 2 (3).
Measure power consumption of the refrigeration plant within 1
hour.
2.
Transition period is 0.5 hour. Change condenser sequence.
Run condenser 2 and condenser 3 at 100 %
capacity. Condenser 1 (VFD) should run as trimming one.
3.
Measure power consumption of
refrigeration plant (new condenser sequence) within 1
hour.
4.
Compare power consumption in
step 1 and in step 3.
Certainly, everybody is interested in energy savings
during long periods of time (months or years). However, refrigeration load during
this period can vary significantly. Correct verification can be done only by
testing during a short period of time. Sometimes, several short period testings
can be done and average energy savings can be estimated.