Before we start a
journey in energy efficiency of industrial refrigeration, it is better to know
our goal. The goal is an ideal (energy efficient) refrigeration plant.
Control of this plant consists of 3
parts:
- Software
to determine optimum operating strategies and optimum set points at any given moment.
- SophisticatedPLC to implement these strategies and
set points.
- VFD
(variable frequency drive) for compressors, condenser fans and evaporator
fans.
Unfortunately, mentioned software doesn’t
exist because it is a very complicated and expensive issue. Fortunately, if we
change operating strategies and operating set points several times per year, we
will be very close to optimum (the most efficient) operation.
What is the most important part of this
control?
I believe that optimum strategies and
optimum set points are the most important part of control for every
refrigeration plant. VFD can save energy, but it less effective than right
strategies and right set points.
Several chief engineers told me that
their companies have bought very expensive (sometimes more than $100,000)
PLC, but they haven’t received energy savings
that were expected. Major reason of this is wrong set points and operating
strategies.
Sophisticated
PLC doesn’t save energy itself; it just helps
us to implement right operating strategies and right set points. These
PLC are good tools, but you have to know how
to use them.
I’ll give you a real life example of
optimum (flexible) operation against traditional (fixed)
operation.
One company has a cooler. Temperature in
this cooler is 50 °F. Three walls have constant exterior temperature of 35 °F.
One wall and roof have ambient exterior temperature. This cooler requires
heating all year around. Two evaporator coils are located inside this cooler and
supplied by discharge hot gas (ammonia) for heating. Set point for minimum
condensing pressure is 130 psig and back pressure regulators (BPR) for these
coils are set to 110 psig. Requirement to keep minimum condensing pressure at
130 psig is a major barrier to reduce this pressure and save energy. This
setting \was unchanged for the last several years. This is a traditional
approach.
Does this cooler require the same amount
of heat all year around? No.
Maximum heat requirement is at winter
time, less heat is required at fall and spring time, and minimum heat
requirement is at summer time.
During fall and spring we can change
settings for minimum condensing pressure and BPR to 120 psig and 105 psig
accordingly.
During summer we can change these
settings to 110 psig and 100 psig accordingly. Not every summer day we can reach
condensing pressure of 110 psig, but this setting will give us opportunity to
float condensing pressure according to refrigeration load and ambient
condition.
New settings will reduce heating capacity
of these coils to match heat requirements and they will give us opportunities to
save energy. To optimize performance of mentioned coils we also have to balance
hot gas supply. This is an efficient (flexible) operation.
As I mentioned, sophisticated
PLC is the good tool. This refrigeration
plant has a good PLC, which gives opportunity
to control operating time of these coils. I suggest keeping this time at 90-95 %
level by reducing minimum set point for condensing pressure.
My estimation has shown that optimization
of minimum set point of condensing pressure will reduce annual energy bill for
this company by $20,000.