Minimum allowable
condensing pressure
Space heating
One of the barriers to reducing minimum
condensing pressure is the heating of high temperature coolers. The heating
process is similar to hot gas defrosting of evaporator coils, only evaporator
fans are running.
First step, to minimize condensing
pressure, is the balancing of heating requirement and capacity of the coil. BPR
(back pressure regulator) setting determines capacity of the
coil.
For
example. Air temperature in the cooler is 50 °F. BPR set to 93
psig (corresponding temperature 60 °F). Temperature difference is 60 – 50
= 10 °F. Capacity of the coil is proportional to the temperature difference. By
changing BPR setting to 103 psig (corresponding temperature 65 °F), temperature
difference increases to 15 °F and capacity of the coil increases
50%.
BPR setting should be changed several
times per year to match the heating requirements. We can have BPR setting 93
psig during the summer (low heating requirement), 98 psig for fall and spring,
and 103 psig during the winter (high heating requirement).
Second step is the balancing capacity
of the coil and hot gas supply. Undersupply of the hot gas will reduce capacity
of the coil and part of this coil will be flooded with liquid refrigerant. If
hot gas is oversupplied, only portion of this gas will condense in the coil and
excessive gas will go through BPR into the suction line as parasitic
refrigeration load. Pressure difference between BPR setting and condensing
pressure determines the hot gas supply. Usually, this pressure difference is 10
– 15 psig.
In our example, summer BPR setting is
93 psig. To mach this lowest capacity of the coil, pressure difference should be
10 psig. Summer minimum allowable condensing pressure will be 93 + 10 = 103
psig.
BPR winter setting is 103 psig. To match
this highest capacity of the coil, pressure difference should be 15 psig. Winter
minimum allowable condensing pressure will be 103 + 15 = 118 psig.
To keep refrigeration plant at peak
efficiency, set points should be changed from time to time, based on real
operating conditions.
In our example, settings should be
changed 3 times per year.
|
BPR (psig) |
Condensing pressure (psig) |
Winter |
103 |
118 |
Spring, Fall |
98 |
111 |
Summer |
93 |
103 |
Traditional constant settings for this
refrigeration plant are BPR-120 psig, condensing pressure -150 psig. Only
variable set points can give us an opportunity to save energy.
Better
result and easier adjustment can be done, if we replace BPR with liquid drainer.
In this case pressure inside the coil will adjust itself and we have to change
just condensing pressure.
We have 2 opportunities to reduce
condensing pressure even further.
1. Run dedicated small compressor for coil
heating and the rest of the refrigeration plant run at optimum lowered
condensing pressure.
2. Run dedicated small compressor as a heat
pump to increase pressure from lowered condensing pressure to 118
psig.